EasyManua.ls Logo

Siemens CU240B-2 - Correcting an Unsuccessful Firmware Upgrade or Downgrade

Siemens CU240B-2
518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Corrective maintenance
8.2 Firmware upgrade and downgrade
Converter with the CU240B-2 and CU240E-2 Control Units
396 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
8.2.3
Correcting an unsuccessful firmware upgrade or downgrade
How does the inverter signal an unsuccessful upgrade or downgrade?
The inverter signals an unsuccessful firmware upgrade or dow
n-
grade by a quickly flashing LED RDY and the lit LED BF.
Correcting an unsuccessful upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
Does the firmware version of your inverter fulfill the preconditions?
For an upgrade, as a minimum V4.5.
For a downgrade, as a minimum V4.6.
Have you correctly inserted the card?
Does the card contain the correct firmware?
Repeat the appropriate procedure.

Table of Contents

Other manuals for Siemens CU240B-2

Related product manuals