Technical data
10.2 Technical data, CU240E-2 Control Unit
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
425
10.2
Technical data, CU240E-2 Control Unit
Feature
Data
Fieldbus interface CU240E-2, CU240E-2 F With RS485 interface for the
following protocols:
USS
Modbus RTU
Article numbers:
Overview of Control Units
(Page 29)
CU240E-2 DP,
CU240E-2 DP-F
With PROFIBUS interface
CU240E-2 PN,
CU240E-2 PN-F
With PROFINET interface
Operating voltage You have two options for the Control Unit power supply:
Supply from the Power Module
External supply via terminals 31 and 32 with 20.4 … 28.8 VDC.
Use a power supply with protective extra low voltage (PELV according to EN 61800-5-1),
Class 2.
The 0 V of the power supply must be connected to the PE of the plant/system through a
low-ohmic connection.
The power supply is electrically isolated from the control terminals.
Current consumption
max 0.5 A
Power loss
5.0 W
Plus power loss of the output voltages.
Output voltages
+24 V out (terminal 9),18 V … 28.8 V, max. 100 mA
+10 V out (terminals 1 and 35), 9.5 V … 10.5 V, max. 10 mA
Setpoint resolution
0.01 Hz
Digital inputs 6 (DI 0 … DI 5)
Low < 5 V, high > 11 V
Electrically isolated
30 V maximum input voltage
5.5 mA current consumption
SIMATIC-compatible
PNP/NPN switchable
10 ms response time for debounce time p0724 = 0.
Pulse input
1 (DI 3)
Maximum frequency 32 kHz
Analog inputs 2 (AI 0, AI 1)
Differential input
12-bit resolution
13 ms ± 1 ms response time
AI 0 and AI 1 can be switched over:
0 V … 10 V or -10 V … +10 V (voltage < 35 V)
0 mA20 mA (120 Ω input resistance, voltage < 10 V, cur-
rent < 80 mA)
If AI 0 and AI 1 are configured as supplementary digital inputs: Volt-
age < 35 V, low < 1.6 V, high > 4.0 V, 13 ms ± 1 ms response time
for debounce time p0724 = 0.