Description
3.4 Components for the Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
38 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
The line reactor supports the
overvoltage protection,
smoothes the harmonics in the line supply and bridges
commutation dips. For the Power Modules subsequen
t-
ly listed, a line reactor is suitable in order to da
m
pen the
specified effects.
Damage to inverter as a result of a missing line reactor
Depending on the Power Module and line supply, if a line reactors is not used, this can
result in damage to the inverter and other components in the electrical plant or system.
• Install a line reactor if the relative short-circuit voltage of the line supply is below 1%
FSA 6SL3224-0BE13-7UA0,
6SL3224-0BE15-5UA0
0.37 kW … 0.55 kW 6SE6400-3CC00-2AD3
6SL3224-0BE17-5UA0,
0.75 kW … 1.1 kW 6SE6400-3CC00-4AD3
FSB 6SL3224-0BE22-2☐A0,
2.2 kW … 3.0 kW 6SL3203-0CD21-0AA0
FSC 6SL3224-0BE25-5☐A0,
7.5 kW … 11.0 kW 6SL3203-0CD22-2AA0
FSD 6SL3224-0BE31-5☐A0,
18.5 kW … 22 kW 6SL3203-0CJ24-5AA0
FSE 6SL3224-0BE33-0☐A0,
37 kW … 45 kW 6SL3203-0CJ28-6AA0
FSF 6SL3224-0BE34-5☐A0,
55 kW … 75 kW 6SE6400-3CC11-2FD0
6SL3224-0BE41-1UA0 132 kW 6SL3000-0CE32-8AA0
GX
6SL3224-0XE41-6UA0,
200 kW … 250 kW 6SL3000-0CE35-1AA0