Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
448 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Power-dependent data, PM240-2 - 600 V
The fuses listed in the following tables are examples of suitable fuses.
Additional components for branch protection:
Branch protection and short-circuit
strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Table 10- 23 PM240-2, IP20, FSD, 3 AC 500 V … 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
11 kW
14 A
15 kW
18 A
18.5 kW
22 A
HO base load power
HO base load input current
HO base load output current
7.5 kW
11 A
11 kW
14 A
15 kW
20 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1 815-0 / 25 A
3NE1 815-0 / 25 A
3NE1 803-0 / 35 A
Power loss without filter
0.32 kW
0.41 kW
0.48 kW
Required cooling air flow
Weight without filter
17 kg
17 kg
17 kg
Table 10- 24 PM240-2, IP20, FSD, 3 AC 500 V … 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
22 kW
25 A
30 kW
33 A
37 kW
40 A
HO base load power
HO base load input current
HO base load output current
18.5 kW
24 A
22 kW
28 A
30 kW
36 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1 803-0 / 35 A
3NE1 817-0 / 50 A
3NE1 818-0 / 63 A
Power loss without filter
Power loss with filter
0.56 kW
0.56 kW
0.72 kW
0.73kW
0.88kW
0.88 kW
Required cooling air flow 55 l/s 55 l/s 55 l/s
Weight without filter
Weight with filter
17 kg
18.5 kg
17 kg
18.5 kg
17 kg
18.5 kg