Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
203
Offset and page index of the parameter numbers
Parameter numbers < 2000
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
Parameter numbers
2000
PNU = parameter number
- offset.
Write the parameter number minus the offset into the PNU
(PKE bit
100).
Write the offset in the page index (IND bit 7 … 0).
Parameter number
Offset
Page index
Hex
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0000 … 1999
0
0 hex
0
0
0
0
0
0
0
0
2000 … 3999
2000
80 hex
1
0
0
0
0
0
0
0
6000 … 7999
6000
90 hex
1
0
0
1
0
0
0
0
8000 … 9999
8000
20 hex
0
0
1
0
0
0
0
0
10000 … 11999
10000
A0 hex
1
0
1
0
0
0
0
0
20000 … 21999
20000
50 hex
0
1
0
1
0
0
0
0
30000 … 31999
30000
F0 hex
1
1
1
1
0
0
0
0
60000 … 61999
60000
74 hex
0
1
1
1
0
1
0
0
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 15 8).
Parameter contents
Parameter contents can be parameter values or connectors.
Table 6- 17 Parameter values in the parameter channel
PWE, 3rd word
PWE, 4th word
Bit 15 … 0
Bit 15 … 8
Bit 7 … 0
0
0
8-bit value
0
16-bit value
32-bit value
Table 6- 18 Connectors in the parameter channel
PWE, 3rd word
PWE, 4th word
Bit 15 … 0
Bit 1510
Bit 9 … 0
Number of the connector 3F hex The index or bit field num-
ber of the connector