Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
215
Signal inter-
connection in
the inverter
0 1 = Ready to start Power supply switched on; electronics ini-
p2080[0] =
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no
fault is active. With the command "Enable
operation" (STW1.3), the inverter switches
p2080[1] =
r0899.1
2 1 = Operation enabled Motor follows setpoint. See control word 1,
p2080[2] =
3 1 = Fault active The inverter has a fault. Acknowledge fault
p2080[3] =
4 1 = OFF2 inactive Coast down to standstill is not active. p2080[4] =
5 1 = OFF3 inactive Quick stop is not active. p2080[5] =
6 1 = Switch-on inhibit active It is only possible to switch on the motor
after an OFF1 followed by ON.
p2080[6] =
7 1 = Alarm active Motor remains switched on; no acknowl-
p2080[7] =
8 1 = Speed deviation within the
Setpoint / actual value deviation within the
p2080[8] =
9 1 = Master control requested The automation system is requested to
accept the inverter control.
p2080[9] =
10
1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corre-
p2080[10] =
11 1 = Torque limit not reached Comparison value for current or torque has
been fallen below.
p2080[11] =
r0056.13 /
12 Reserved p2080[12] =
13 0 = Alarm, motor overtemperature -- p2080[13] =
14
1 = Motor rotates clockwise
Internal inverter actual value > 0
p2080[14] =
r2197.3
0 = Motor rotates counterclock-
Internal inverter actual value < 0
15 0 = Alarm, inverter thermal over-
p2080[15] =
If you change over from another telegram to telegram 20, then the assignment of the previous
Further information about USS is provided in the "Fieldbus" function manual.
Overview of the manuals (Page 507)