Advanced commissioning
6.7 Application-specific functions
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
277
Restrictions for the unit changeover function
The values on the rating plate of the inverter or motor cannot be displayed as percentage
values.
Using the unit changeover function several times (for example, percent → physical unit 1
→ physical unit 2 → percent) may lead to the original value being changed by one decimal
place as a result of rounding errors.
If the unit is changed over into percent and the reference value is then changed, the
percentage values relate to the new reference value.
Example:
For a reference speed of 1500 rpm, a fixed speed of 80% corresponds to a speed of
1200 rpm.
If the reference speed is changed to 3000 rpm, then the value of 80% is kept and now
means 2400 rpm.
Reference variables for unit changeover
p2000 Reference frequency/speed
p2001 Reference voltage
p2002 Reference current
p2003 Reference torque
r2004 Reference power
p2005 Reference angle
p2006 Reference temperature