Advanced commissioning
6.7 Application-specific functions
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
325
Table 6- 46 Response options for load monitoring
p2181 = 0
Load monitoring deactivated (factory setting)
p2181 = 1
A07920 for torque/speed too low
p2181 = 2
A07921 for torque/speed too high
p2181 = 3
A07922 for torque/speed out of tolerance
p2181 = 4 F07923 for torque/speed too low
p2181 = 5
F07924 for torque/speed too high
p2181 = 6
F07925 for torque/speed out of tolerance
p2181 = 7
Pump/fan load monitoring as alarm
p2181 = 8
Pump/fan load monitoring as fault
The settings in p2193 for pumps/fans (p2193 = 4 or 5) are only permissible with the settings
for load monitoring for pumps/fans (p2181 = 7 or 8)