Backing up data and series commissioning
7.2 Saving settings on a PC
Converter with the CU240B-2 and CU240E-2 Control Units
364 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
PC/PG
inverter
The procedure depends on whether you also transfer settings of safety functions or not.
Procedure with STARTER without enabled safety functions
To load the settings from the PG to the inverter with STARTER, proceed as follows:
1. Go online:
.
2. Click the "Download project to target system" button: .
3. Wait until STARTER reports that loading has been completed.
4. To save the data to the non-volatile memory of the inverter, select the "Copy RAM to
ROM" button:
.
5. Go offline:
.
You have transferred the settings from the PG to the inverter with STARTER.
Procedure with Startdrive without enabled safety functions
To transfer the settings from the PG to the inverter with Startdrive, proceed as follows:
1. Go online.
2. Select "Load to device" > "Hardware and software" from the shortcut menu.
3. Wait until Startdrive reports that loading has been completed.
4. Go offline.
5. Confirm the dialog box that then opens by clicking "Yes" to save the data to the non-
volatile memory of the inverter (Copy from RAM to ROM).
You have transferred the settings from the PG to the inverter with Startdrive.