Backing up data and series commissioning
7.2 Saving settings on a PC
Converter with the CU240B-2 and CU240E-2 Control Units
366 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Procedure with Startdrive
To transfer the settings from the PG to the inverter with Startdrive and activate the safety
functions, proceed as follows:
1. Save the project.
2. Select "Load to device."
Image 7-1 Activating settings in Startdrive
3. Connect Startdrive online with the drive.
4. Click the "Start safety commissioning" button.
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Click the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter supply voltage again.
You have transferred the settings from the PG to the inverter with Startdrive and have
activated the safety functions.