Backing up data and series commissioning
7.5 Write and know-how protection
Converter with the CU240B-2 and CU240E-2 Control Units
374 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Proceed as follows to activate know-how protection:
Select the inverter in the STARTER project and select "Know
-
how protection drive device
/ Activate …" in the shortcut menu.
Write protection (Page 370)
Enter your password. Length of the
password: 1
… 30 characters.
For the password, we recommend
that you only use characters from
the ASCII character set. If you use
any character for the password,
then if changes
are made to the
Windows language settings after
activating know
-how protection,
errors can occur when subsequen
t-
ly checking the password.
, press the "Copy RAM to ROM" button. This means that you save
your settings so that they are protected against power failure.
You have activated know-how protection.
Backing up settings on the memory card
When know-how protection is activated, you can save the settings to the memory card using
p0971.
To do this, set p0971 = 1. The data is written to the memory card encrypted. After saving,
p0971 is reset to 0.
Deactivating know-how protection, deleting a password
Preconditions
● You are online with STARTER.
● You have inserted the recommended Siemens card.
Overview of Control Units (Page 29)