Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
466 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Table 10- 45 PM230, IP20, frame sizes D, 3 AC 380 V … 480 V
Article No. - without filter
Article No. - with filter
6SL3210…
6SL3210…
…1NE24-5UL0
1NE24-5AL0
1NE26-0UL0
1NE26-0AL0
LO base load power
LO base load input current
LO base load output current
22 kW
42 A
45 A
30 kW
56 A
60 A
HO base load power
HO base load input current
HO base load output current
18.5 kW
36 A
38 A
22 kW
42 A
45 A
Fuse according to IEC
Fuse according to UL
3NE1818-0
3NE1818-0
3NE1820-0
3NE1820-0
Power loss
0.52 kW
0.68 kW
Required cooling air flow
80 l/s
80 l/s
Cross section of line and motor cables 1635 mm
2
5 … 2 AWG
1635 mm
2
5 … 2 AWG
Tightening torque for line and motor cables
6 Nm / 53 lbf in
6 Nm / 53 lbf in
Weight without filter
Weight with filter
11 kg
14 kg
11 kg
14 kg
Table 10- 46 PM230, IP20, frame sizes E, 3 AC 380 V … 480 V
Article No. - without filter
Article No. - with filter
6SL3210…
6SL3210…
1NE27-5UL0
1NE27-5AL0
…1NE28-8UL0
…1NE28-8AL0
LO base load power
LO base load input current
LO base load output current
37 kW
70 A
75 A
45 kW
84 A
90 A
HO base load power
HO base load input current
HO base load output current
30 kW
56 A
60 A
37 kW
70 A
75 A
Fuse according to IEC
Fuse according to UL
3NE1021-0
3NE1021-0
3NE1022-0
3NE1022-0
Power loss 0.99 kW 1.2 kW
Required cooling air flow
80 l/s
80 l/s
Cross section of line and motor cables 25 50 mm
2
3 … 1-1/0 AWG
2550 mm
2
3 … 1-1/0 AWG
Tightening torque for line and motor cables 6 Nm / 53 lbf in 6 Nm / 53 lbf in
Weight without filter
Weight with filter
15 kg
22 kg
15 kg
22 kg