Description
3.5 Supported motor series
Converter with the CU240B-2 and CU240E-2 Control Units
50 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Some restrictions apply for operation:
Table 3- 7 Restrictions for operation with encoderless synchronous motors
Firmware Firmware version ≥ FW V4.7
Applications Suitable for applications for steady-state operation in the range of the
rated motor speed:
• Conveyor drives
• Pumps
• Fans
Speed of the motor
• Speed ≤ rated motor speed
Operation is not permitted in field weakening.
• In steady-state operation ≥ 15% of the rated speed.
For accelerating and reversing functions, speeds 0 … 15% of the rat-
Switching on when motor
The "flying restart" function is not possible.
Only "STO" is permitted by the safety functions integrated in the drive.
Ambient temperature of
motor
≤ 40° C
The inverter monitors the motor using a temperature model. The tem-
perature model presumes an ambient temperature of 40° C.
In the case of higher ambient temperatures, the inverter will no longer be
able to provide sufficient protection for the motor. If you operate the
motor in ambient temperatures > 40° C, you must reduce the power of
the motor sufficiently.
Information on temperature-dependent power de-rating can be found in
A multi-motor drive, i.e. simultaneously operating several motors connected to one inverter,
is permissible for standard induction motors in installations according to IEC.
Further information is provided in the Internet:
Multi-motor drive (http://support.automation.siemens.com/WW/view/en/84049346)