Installing
4.2 Connecting inverters in compliance with EMC
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
55
For screw connections onto painted or anodized surfaces, establish a good conductive
contact using one of the following methods:
Use special (serrated) contact washers that cut through the painted or anodized
surface.
Remove the insulating coating at the contact locations.
Equip the following components with interference suppression elements:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Interference suppression elements include RC elements or varistors for AC-operated
coils and freewheeling diodes for DC-operated coils.
Connect the interference suppression element directly at the coil.
Radio interference suppression
Connect interference suppressors to all contactors, relays, solenoid valves and motor
holding brakes directly at the coil in order to dampen high-frequency radiation when these
devices are switched off. Use RC elements or varistors for AC-operated coils and
freewheeling diodes or varistors for DC-operated coils.
Cable routing and shielding
Cables in the control cabinet
Route the power cables of the drive so that there is a minimum clearance of 25 cm to
signal and data cables. Power cables are line, DC link and motor cables as well as
connecting cables between the Braking Module and braking resistor. Alternatively,
implement the separation using metal partitions connected to the mounting plate through
a good electrical connection.
Route power cables with low noise levels separately from power cables with high noise
levels
Power cables with low noise level:
- line cables from the line to the line filter
Power cables with high noise level:
- cables between the line filter and inverter
- DC link cables
- cables between the Braking Module and braking resistor
- motor cables
Route the cables so that signal and data cables as well as power cables with low noise
level only cross power cables with a high noise level at right angles.
Keep all cables as short as possible.
Route the cables as close as possible to grounded enclosure parts such as mounting
plates or the cabinet frame.