7ML19985QT81 XRS-5 Series Transducers – OPERATION MANUAL Page EN-5
English
Mounting
Mount the transducer so that it is above the maximum material level by more than the
blanking value for accurate results. Refer to the associated transceiver manual for
information on setting the blanking value.
The transducer must be mounted so that the axis of transmission is perpendicular to the
liquid’s surface.
Do not over tighten mounting. Hand tightening of the mounting hardware is sufficient.
Consider the optional temperature sensor when mounting the transducer.
Suspended Conduit Bracket
Flexible conduit transducer should not be
subjected to wind, vibration or jarring.
Submersible Plywood
Submersible transducer, used in
applications where flooding is possible.
Plywood mounting provides excellent isolation,
but must be rigid enough to avoid flexing if
subjected to loading.
rigid metal
conduit
coupling
transducer
steel channel
coupling
transducer
fl
ex
ibl
e con
d
u
i
t
rigid metal
conduit
coupling
submergence
shield
coupling