Alarms 5-7SIMATIC PCS 7 OSx 4.1.2 Operator
Acknowledging Non-networked Alarm Tags If a tag configured for
alarming has a non-networked status attribute, such as a recipe area tag,
and the tag goes into alarm, the system does not clear the alarm
unacknowledged bit of the status w ord under the following conditions:
The operator does not acknowledge the alarm, and
ThesystemtransitionsfromtheOperatestatetotheOfflinestateand
then back to the Operate state.
Typically, tags configured for alarming have networked status attributes,
and this situation does not occur. However, the status attribute for recipe
area tags is not networkable. For e xample, a recipe area tag goes into
alarm, and the operator does not acknowledge the alarm before the system
state transitions from Operate to Offline and then back to Operate again. If
an operator displays a graphic that contains the recipe area tags status
attribute, the alarm unacknowledged bit for the attribute is on, even though
there are no current alarms to acknowledge for the recipe area tag.
When this situation occurs, the operator can ignore the setting of the alarm
unacknowledged bit.

Table of Contents

Other manuals for Siemens SIMATIC PCS 7 OSx

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 OSx and is the answer not in the manual?

Siemens SIMATIC PCS 7 OSx Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7 OSx
CategoryControl Systems
LanguageEnglish

Related product manuals