Parameter
Description Data Read/write
n931
G2_STW
2931
Parameter is only necessary for the parameter model of
PROFIdrive V3 standard. Parameter is only visible if
PROFIdrive V3 is set.
Dec.Plc.: 0
Unit: -
Indices: -
Type: V2
Menus:
- Parameter menu
- Upread/free access
n932
G2_XIST1
2932
Parameter is only necessary for the parameter model of
PROFIdrive V3 standard. Parameter is only visible if
PROFIdrive V3 is set.
Dec.Plc.: 0
Unit: -
Indices: -
Type: X4
Menus:
- Parameter menu
- Upread/free access
U933*
SR Mode
2933
Function parameter for specifying the operating mode of
the shift register:
0 = Shifting
1 = Ring buffer
Index 1: Shift register 1 [FD787a]
Index 2: Shift register 2 [FD787b]
If the parameter is changed a reset is implicitly carried out.
index1: 0
Min: 0
Max: 1
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U934*
SR MemDepth
2934
Function parameter for specifying the memory depth of
the shift register
Index 1: Shift register 1 [FD787a]
Index 2: Shift register 2 [FD787b]
The number of internally used storage elements is
calculated from (memory depth + 1) and is thus between
1 and 50.
Due to the separate clock inputs for write and read, the
actual (internal) memory depth can deviate from the value
of the function parameter.
If the parameter is changed a reset is implicitly carried out.
index1: 0
Min: 0
Max: 49
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U935*
Src SR InputBi
2935
Data input binectors shift register
Index 1-8: Shift register 1 [FD787a]
Index 9-16: Shift register 2 [FD787b]
index1: 1
Unit: -
Indices: 16
Type: L2 ,B
Menus:
- Parameter menu
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U936*
Src SR InputKK
2936
Input double-word connector shift register
Index 1: Data input shift register 1
Index 2: Correction value shift register 1
Index 3: Value of data output shift register 1
Index 1 - 3: [FD787a]
Index 4: Data input shift register 2
Index 5: Correction value shift register 2
Index 6: Value of data output shift register 2
Index 4 - 6: [FD787b]
index1: 0
Unit: -
Indices: 6
Type: L2 ,K
,K
Menus:
- Parameter menu
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
251
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control