Cause: A data save in the non-volatile memory was not able to be successfully carried out.
- Non-volatile memory is defective.
-
Insu󹪟cient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - Try to save again.
- Replace the memory card or Control U
nit.
F01110 CU: More than one SINAMICS G on one Control Unit
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: More than one SINAMICS G type power unit is being operated from the Control Unit.
F
ault value (r0949, interpre
t decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy: Only one SINAMICS G drive type is permitted.
F01111 CU: Mixed operation of drive units illegal
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: Illegal operation of various drive units on one Control Unit:
- SIN
AMICS S toget
her with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the 󹪝rst drive object with a di󹪜erent power unit type.
Remedy: Only power units of one particular drive type may be operated with one Control Unit.
F01120 Terminal initialization has failed
Message class: Hardware/software error (1)
Message value: %1
Variant: S200 PTI
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: An internal software error occurred while the terminal functions were being initialized.
F
ault value (r0949, interpre
t hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - Carry out a POWER ON (switch-o󹪜/switch-on) for all components.
- U
pgrade 󹪝rmware to later version.
- Contact Technical Support.
- Replace the Control Unit.
F01122 Frequency at the measuring probe input too high
Message class: Application/technological function faulted (17)
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
344 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA