Message value: %1
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The frequency of the pulses at the measuring probe input is too high.
F
ault value (r0949, interpre
t decimal):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
8: DI/DO 13 (X132.8)
16: DI/DO 14 (X132.10)
32: DI/DO 15 (X132.11)
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy: Reduce the frequency of the pulses at the measuring probe input.
F01123 Power unit does not support digital inputs/outputs
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: -
Component: Power Unit
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The power unit does not support the activated "Digital inputs/outputs" function.
Remedy: Deactivate function.
F01150 CU: Number of instances of a drive object type exceeded
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: Drive object type: %1, number permitted: %2, actual number: %3
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The maximum permissible number of instances of a drive object type was exceeded.
No
te regar
ding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex:
aa = drive object type:
- Drive object type (p0107), for which the maximum permissible number of instances was exceeded.
bb = number permitted:
- Maximum permissible number of instances for this drive object type.
cc = actual number:
- Actual number of instances for this drive object type.
dd = no signi󹪝cance
Remedy: - Switch o󹪜 the unit.
- Suitably res
trict the number of instances of a drive object type by reducing the number of inserted components.
- Re-commission the unit.
F01151 CU: Number of drive objects of a category exceeded
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: Drive object category: %1, number permitted: %2, actual number: %3
Component: None
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 345