Dependency: See also: r0032
Note
The mechanical active power is a
vailable smoothed (r0032 with 100 ms, r0082[1] with 1 ms) and unsmoothed
(r0082[0]).
For index [3]:
Smoothing time constant = 0.25 ms
r0196[0...255].0...15 Topology component status
Data type: Unsigned32 Visible in: Extended display
R
ead permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Parame
ter group: Diagnostics general
Unit: -
Description: Displays the status of the components.
r0196[0]: Group status of all components
r0196[1]: S
tatus of component with component number 1
...
r0196[255]: Status of component with component number 255
Bit array: Bit Signal name 1 signal 0 signal
00 Component status bit 0 High Low
01 Component status bit 1 High Low
02 Component status bit 2 High Low
03 Component status bit 3 High Low
04 Component state Active Inactive/parking
06 Topology problem active Yes No
07 Part of the target topology Yes No only act topo
08 Alarm present Yes No
09 Safety message present Yes No
10 Fault present Yes No
11 Alarm class bit 0 High Low
12 Alarm class bit 1 High Low
13 Maintenance required Yes No
14 Maintenance urgently required Yes No
15 Fault gone/can be acknowledged Yes No
Note
F
or bit 03 ... 00:
Bit 3, 2, 1, 0 = 0, 0, 0, 0 --> com
ponent no
t a
v
ailable.
Bit 3, 2, 1, 0 = 0, 0, 0, 1 --> run up, acyclic communications (LED = orange).
Bit 3, 2, 1, 0 = 0, 0, 1, 0 --> operating mode, cyclic communications (LED = green).
Bit 3, 2, 1, 0 = 0, 0, 1, 1 --> alarm (LED = green).
Bit 3, 2, 1, 0 = 0, 1, 0, 0 --> fault (LED = red).
Bit 3, 2, 1, 0 = 0, 1, 0, 1 --> detection via LED and operating mode (LED = green/orange).
Bit 3, 2, 1, 0 = 0, 1, 1, 0 --> detection via LED and alarm (LED = green/orange).
Bit 3, 2, 1, 0 = 0, 1, 1, 1 --> detection via LED and fault (LED = red/orange).
Bit 3, 2, 1, 0 = 1, 0, 0, 0 --> 󹪝rmware being downloaded (LED = green/red with 0.5 Hz).
Bit 3, 2, 1, 0 = 1, 0, 0, 1 --> 󹪝rmware download completed, wait for POWER ON (LED = green/red with 2.0 Hz).
For bits 12 ... 11:
These status bits are used for the classi󹪝cation of internal alarm classes and are intended for diagnostic purposes only
on certain automation systems with integrated SINAMICS functionality.
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 599