p0215 = 3:
An externally connected br
aking resistor is controlled and also thermally monitored per software.
Parameters p0216, p0218 and p0219[0] and p0219[1] must be set in order that the monitoring functions. Chopper
operation is not possible if the values are not set.
p0215 = 10:
The externally connected braking resistor is not monitored.
The internal braking resistor is monitored.
p0216 Braking resistance value
Data type: FloatingPoint32 Visible in: Extended display
R
ead permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Commissioning
Par
ameter group: Dynamic braking, Quick commissioning
Unit: ohm
Min:
0.0 [ohm]
Max:
1000.0 [ohm]
Factory setting:
0.0 [ohm]
Description: Sets the resistance value of a connected external braking resistor.
Dependency: The parameter is only relevant for p0215 = 2, 3.
p0218 Braking resistor maximum power duration
Data type: FloatingP
oint32 V
isible in: Ext
ended displa
y
R
ead permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Commissioning
Par
ameter group: Dynamic braking, Quick commissioning
Unit: s
Min:
0.00 [s]
Max:
2000.00 [s]
Factory setting:
0.00 [s]
Description: Sets the maximum duration when operating the braking resistor at its maximum power level.
Dependency: The parameter is only relevant for p0215 = 2, 3.
p0219[0...1] Braking resistor braking power
Data type: FloatingPoint32 Visible in: Extended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Commissioning
Par
ameter group: Dynamic braking, Quick commissioning
Unit: kW
Min:
0.00 [kW]
Max:
20000.00 [kW]
Factory setting:
0.00 [kW]
Description: Sets the braking power of the connected braking resistor.