r0755[0...1] Analog inputs, actual value in percent
S200 PTI Data type: FloatingPoint32 Visible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Parame
ter group: Analog inputs
Unit: %
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals ar
e referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Note
AI: Analog Input
p0756[0...1] Analog inputs type
S200 PTI Data type: Integer16 Visible in: St
andard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog inputs
Unit: -
Min:
0
Max:
4
Factory setting:
[0] 4
[1] 4
Description: Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a volt
age input (r0752, p0757, p0759 are displayed in V).
Value: 0: Unipolar voltage input (0 V ... +10 V)
1: Unipolar voltage input monitored (+2 V ... +10 V)
4: Bipolar voltage input (-10 V ... +10 V)
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
WARNING
The maximum voltage di󹪜erence between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
Note
When
c
hanging
p0756,
t
he parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten with
the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
p0757[0...1] Analog inputs characteristic value x1
S200 PTI Data type: FloatingPoint32 Visible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog inputs
Unit: -
Min:
-50.000
Max:
160.000
Factory setting:
0.000
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 621