p0760[0...1] Analog inputs characteristic value y2
S200 PTI Data type: FloatingPoint32 Visible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog inputs
Unit: %
Min:
-1000.00 [%]
Max:
1000.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteris
tic for the analog inputs is de󹪝ned using 2 points.
This parameter speci󹪝es the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Note
The parameters f
or the characteristic do not have a limiting e󹪜ect.
p0761[0...1] Analog inputs wire break monitoring, response threshold
S200 PTI Data type: FloatingP
oint32 V
isible in: S
t
andar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog inputs
Unit: -
Min:
0.00
Max:
10.00
Factory setting:
2.00
Description: Sets the response threshold for the wire breakage monitoring of the analog inputs.
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (monit
ored unipolar voltag
e input (+2 V ... +10 V)), unit [V].
See also: p0756
Note
AI: Analog Input
p0762[0...1] Analog inputs wire-break monitoring delay time
S200 PTI Data type: Unsigned16 Visible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog inputs
Unit: ms
Min:
0 [ms]
Max:
1000 [ms]
Factory setting:
100 [ms]
Description: Sets the delay time for the wire breakage monitoring of the analog inputs.
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 623