Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Note
AI: Analog Input
p0763[0...1] Analog inputs o󹪜set
S200 PTI Data type: FloatingPoint32 V
isible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog outputs
Unit: -
Min:
-20.000
Max:
20.000
Factory setting:
0.000
Description: Sets the o󹪜set for the analog in
puts.
The o󹪜set is added to the input signal before the scaling characteristic.
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Note
AI: Analog Input
p0764[0...1] Analog inputs dead zone
S200 PTI Data type: FloatingPoint32 Visible in: Standar
d display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Can be
changed in the operating
state:
Operation
Par
ameter group: Analog outputs
Unit: -
Min:
0.000
Max:
20.000
Factory setting:
0.000
Description: Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts wit
h the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index: [0] = AI0 (X132.19/20)
[1] = AI1 (X132.21/22)
Note
AI: Analog Input
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
624 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA