p29340 Warning 1 assigned to digital output
Data type: Integer16 Visible in: St
andard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or drive applications
Can be
changed in the operating
state:
Ready for oper
ation
Parameter group: Technology Extensions, I/O conguration
Unit: -
Min:
1
Max:
5
Fact
ory setting:
1
Description: Denes conditions for WARNING1.
1: Motor o
verload protection warning: 85% of motor overload threshold has been reached.
2: Fan warning: The predicted lifespan of the fan has expired. Replacement is needed.
3: Encoder error
4: Motor overtemperature warning.
5: Capacitor warning: The service life of the capacitor has expired. Replacement is needed.
Value: 1: Motor overload protection
2: Fan life time
3: Encoder error
4: Motor overtemperature
5: Capacitor life time
p29341 Warning 2 assigned to digital output
Data type: Int
eg
er16 V
isible in: S
t
andard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or drive applications
Can be
changed in the operating
state:
Ready for oper
ation
Parameter group: Technology Extensions, I/O conguration
Unit: -
Min:
1
Max:
5
Fact
ory setting:
3
Description: Denes conditions for WARNING2.
1: Motor overload protection warning: 85% of motor overload threshold has been reached.
2: Fan warning: The predicted lifespan of the fan has expired. Replacement is needed.
3: Encoder error
4: Motor overtemperature warning.
5: Capacitor warning: The service life of the capacitor has expired. Replacement is needed.
Value: 1: Motor overload protection
2: Fan life time
3: Encoder error
4: Motor overtemperature
5: Capacitor life time
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 729