Section Settings Description
[processing_
loginphase]
StartState= Specifies whether the PCU Installer is active before the Desktop runs up.
The setting StartState=activated is required, in particular, if an installation re‐
quires a cold start.
Possible values:
activated PCU Installer starts setups
stopped PCU Installer is stopped completely
continueSetups= Some setups can only be completed after the system has been restarted. In this case,
the PCU Installer waits until you restart the PC system.
You can specify here whether such setups are to be continued after a restart.
(See also: Note: Troubleshooting for incorrect installation routines (Page 116))
Possible values: yes; no
scanSetupDirs= Specifies whether setup directories are to be checked and, if required, setup files
executed before the Desktop run-up.
The following directories are checked if this setting has been activated:
Local setup directories from the [local_setupdirs] setting are always checked.
You can define separately whether additional directories on removable disks or
in the network are to be checked. (See settings "scanRemovableDriveSetupDirs"
and "scanNetworkDriveSetupDirs")
If you deactivate this setting, neither local directories, nor directories on removable
disks or in the network are checked, i.e. the setting scanSetupDirs=no overwrites, for
example, scanNetworkDriveSetupDirs=yes.
Possible values: yes; no
scanRemovableDrive
SetupDirs=
Specifies whether directories on removable disks are to be checked from the setting
[removable_setupdirs] and, if required, setup files executed before the Desktop run-
up.
The setting "scanSetupDirs" must also be activated so that these directories are
checked.
Possible values: yes; no
scanNetworkDrive
SetupDirs=
Specifies whether network directories are to be checked from the setting [net_setup‐
dirs] and, if required, setup files executed before the Desktop run-up.
The setting "scanSetupDirs" must also be activated so that these directories are
checked.
Possible values: yes; no
waitTimeDevicesDete
ction=
Specifies the maximum wait time for device detection (removable media) in the system
run-up. This setting is only relevant if the PCU Installer searches for setups on remov‐
able media prior to the desktop run-up. (See settings "scanSetupDirs", "scanRemo‐
vableDriveSetupDirs" in the section [processing_loginphase] and section [remova‐
ble_setupdirs])
Possible values:
Positive integer (milliseconds)
infinite
waitTimeDriveLetter
sAssignment=
Specifies how long the PCU Installer will wait during the system run-up until the system
has assigned a drive letter to all of the logical drives. This setting is only relevant if the
PCU Installer searches for setups on removable media prior to the desktop run-up.
(See settings "scanSetupDirs", "scanRemovableDriveSetupDirs" in the section [pro‐
cessing_loginphase] and section [removable_setupdirs])
Possible values:
Positive integer (milliseconds)
infinite
Installing and configuring updates and automation software
5.9 PCU Installer
PCU Base Software (IM10)
114 Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals