Addr. Parameter C Setting Options Default Setting
_:2461:3 Supv. sum V:Threshold 0.300 V to 170.000 V 25.000 V
_:2461:6 Supv. sum V:Delay
failure indication
0.00 s to 100.00 s 5.00 s
VT miniatureCB
_:2641:101 VT minia-
tureCB:Response time
0.00 s to 0.03 s 0.00 s
Measuring Point V-1ph
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated primary
voltage
0.200 kV to 1200.000 kV 400.000 kV
_:2311:102 General:Rated secondary
voltage
80 V to 340 V 100 V
_:2311:108 General:Matching ratio
Vph / VN
0.10 to 9.99 1.73
_:2311:103 General:Tracking
inactive
active
inactive
_:2311:130 General:Measuring-point
ID
0 to 100 0
VT 1
_:3811:103 VT 1:Magnitude correc-
tion
0.010 to 10.000 1.000
_:3811:108 VT 1:Phase
V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
VN broken-delta
_:3811:107 VT 1:Sequence number
device
1 to 2147483647 2147483647
VT miniatureCB
_:2641:101 VT minia-
tureCB:Response time
0.00 s to 0.03 s 0.00 s
Power-System Data
5.8 Settings
130 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC