EasyManuals Logo

Siemens SIPROTEC 5 User Manual

Siemens SIPROTEC 5
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
(1) If the setting Range active is set to test , the setting Transformation ratio is not
displayed.
(2) If the setting Range active is set to false, the settings Upper limit, Transformation
ratio upper limit, Lower limit and Transformation ratio are not displayed.
Measured-Value Calculation
The function 20-mA channel processes a single 20-mA current signal supplied by the 20-mA unit of the corre-
sponding channel. The 20-mA current measured value is converted into the correct physical quantities such as
temperature or pressure. In each 20-mA functional unit (Ether. and serial) there are always 12 of the 20-mA
channel function blocks, even if fewer channels are connected with the 20-mA unit. The calculated values are
available for further processing via CFC, GOOSE, protocols, and the display image.
Measured-Value Processing
The 20-mA unit typically transmits a value which represents a physical quantity, such as a temperature or a
pressure. Therefore, the device must contain a characteristic curve that maps the physical quantity to the 20-
mA value. If you do not activate the Range active setting (no x in the check box), the function operates
over the range 0 mA to 20 mA. If a value smaller than 0 mA or greater than 20 mA is active at the input of the
20-mA unit, the measured value is identified as invalid. The setting of the range for the scaled value goes from
a usable range of 0 mA to 20 mA. The following figure shows an example.
[sckanumw-190214-01, 1, en_US]
Figure 6-36 Settings for Example 1
In this example, the measured value 0 mA means a temperature of 0 °C and the measured value 20 mA means
a temperature of 100 °C. So enter as Unit = °C and Conversion factor = 100. The resolution (decimal
place) of the temperature value can be chosen; for a decimal place, select Resolution = 0.1.
[dwknges3-020513-01.tif, 1, en_US]
Figure 6-37 Characteristic Curve of a 20-mA Input (Example 1)
Function-Group Types
6.5 Function-Group Type Analog Units
176 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC

Related product manuals