Addr. Parameter C Setting Options Default Setting
_:9781:121 Trig. I RMS 1:Min. phs A 1 A @ 100 Irated 0.030 A to 100.000 A 0.800 A
5 A @ 100 Irated 0.15 A to 500.00 A 4.00 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.800 A
5 A @ 50 Irated 0.15 A to 250.00 A 4.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.800 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 4.000 A
_:9781:122 Trig. I RMS 1:Min. phs B 1 A @ 100 Irated 0.030 A to 100.000 A 0.800 A
5 A @ 100 Irated 0.15 A to 500.00 A 4.00 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.800 A
5 A @ 50 Irated 0.15 A to 250.00 A 4.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.800 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 4.000 A
_:9781:123 Trig. I RMS 1:Min. phs C 1 A @ 100 Irated 0.030 A to 100.000 A 0.800 A
5 A @ 100 Irated 0.15 A to 500.00 A 4.00 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.800 A
5 A @ 50 Irated 0.15 A to 250.00 A 4.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.800 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 4.000 A
_:9781:114 Trig. I RMS 1:Min. hyste-
resis
1.010 p.u. to 1.100 p.u. 1.020 p.u.
dM/dt rise (/Filter time)
_:9781:103 Trig. I RMS 1:+dM/dt
active
no
yes
no
_:9781:107 Trig. I RMS 1:+dM/dt
(Non-phs sel.)
1 A @ 100 Irated 0.030 A to 100.000 A 0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A 1.50 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.300 A
5 A @ 50 Irated 0.15 A to 250.00 A 1.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.500 A
_:9781:124 Trig. I RMS 1:+dM/dt phs
A
1 A @ 100 Irated 0.030 A to 100.000 A 0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A 1.50 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.300 A
5 A @ 50 Irated 0.15 A to 250.00 A 1.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.500 A
_:9781:125 Trig. I RMS 1:+dM/dt phs
B
1 A @ 100 Irated 0.030 A to 100.000 A 0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A 1.50 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.300 A
5 A @ 50 Irated 0.15 A to 250.00 A 1.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.500 A
_:9781:126 Trig. I RMS 1:+dM/dt phs
C
1 A @ 100 Irated 0.030 A to 100.000 A 0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A 1.50 A
1 A @ 50 Irated 0.030 A to 50.000 A 0.300 A
5 A @ 50 Irated 0.15 A to 250.00 A 1.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.500 A
Fault Recorder
7.5 Trigger Functions 3-Phase
SIPROTEC 5, Fault Recorder, Manual 327
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC