Figure 3-48
Example for the Threshold Value of the Voltage Trigger Tripping Stage (Edit Mode: Secondary)
Threshold-Value Setting in an Example of the Current Transformer
If you only want to work in the secondary view, DIGSI 5 supports you if the transformer ratio changes during
the project phase.
In the example the following parameters are set according to the current transformer ratio of 1000 A/1 A . The
parameter dM/dt drop (/Filter time) has a setting value of 0.300 A (see the following image).
System Functions
3.7 General Notes for Setting the Threshold Value of Trigger Functions
SIPROTEC 5, Fault Recorder, Manual 99
C53000-G5040-C018-5, Edition 11.2017