Description of the software
6.4 Description of the menu commands
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
115
The "Cancel configuration release" menu command can then only be selected if a safety
relay is opened online and the safety relay is in "Configuring mode".
6.4.3.7 Configuring mode
Using the "Target system" > "Configuring mode" menu command, the operating mode of the
target system is switched to configuring mode:
The connected MSS is put into "Configuring mode".
In this mode, there is no logic processing.
The safety relay is ready to accept new configuration data.
6.4.3.8 Test mode
Using the "Target system" > "Test mode" menu command, you switch the operating mode of
the target system to test mode.
You can use this operating mode for support when carrying out the prescribed function test
of the safety circuit. For example, you can force the outputs of functions in test mode.
To switch to test mode, you must enter the password for "Switching to test mode".
The "Test mode" menu command can then only be selected if a safety relay is opened online
and the safety relay is in "Configuring mode".
The configuration is fault-free (does not have to be released).
WARNING
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
In this operating mode, the safety program is executed and the outputs are controlled
according to the safety program.
For this reason, you must ensure that the safety of your system is ensured by means of
organizational measures.
6.4.3.9 Safety mode
Using the "Target system" > "Safety mode" menu command, you switch the operating mode
of the target system to safety mode.
In safety mode, the configured safety circuit is active. The outputs are controlled according to
the "Circuit parameter assignment" (= circuit diagram).
The "Safety mode" menu command can then only be selected if a safety relay is opened
online and the safety relay is in "Configuring mode". The configuration must be fault-free and
released.