Description of the software
6.5 Identification and configuration
Modular Safety System 3RK3
134 System Manual, 10/2008, 926 2530-02 DS 02
In this dialog window, the following parameters are shown:
In online mode: The parameters of the uploaded module.
Editable parameters
The parameters are described in the following table:
Parameter name Parameter value
Configuration
Module The designation of the selected module is displayed here. The field has a gray
background and cannot be changed by the user.
Order No. The order number of the selected module is shown here. The field has a gray
background and cannot be changed by the user.
Firmware The firmware of the selected module is shown here. The field has a gray
background and cannot be changed by the user.
Equipment identifier Here you can specify a user-defined equipment identifier (max. 32 characters)
for the selected module and assign it to inputs and outputs.
Inputs The number of inputs of the selected module is shown here.
Outputs The number of outputs of the selected module is shown here.
6.5.2.6 Messages during the consistency check - Configuration
The following HW configuration messages exist:
Message Type Message text Remedy
The expansion modules
must be configured in
succession.
Error "Configuration: There is a gap before
an expansion module."
Correct the configuration "manually",
possibly context menu function
"Delete blank rows automatically".
The central unit must be
available.
Error "Configuration: A central unit always
needs to be configured at slot 3."
Drag the central unit from the catalog
window to slot 3 in the configuration
table.