Operator control
7.3 Planning/configuring
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
217
WARNING
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
In this operating mode, the safety program is executed and the outputs are controlled
according to the safety program.
For this reason, you must implement organizational measures (e.g. warning signs, barriers
etc.) to ensure that the system is safe.
Note
A consistent configuration is the requirement for switching to test mode.
Note
If you have not yet assigned a password, you must assign one now.
The default password is: 0000
Execute the following steps to switch to test mode:
Step Action Result
1 Go online with the menu command "Switching
device" > "Open online".
2 Choose "Target system" > "Test mode" and confirm
the message "Activate test mode" with "Yes".
The "Change password for test mode" dialog box opens.
3 Enter the password for test mode or assign a
password.
The MSS changes from configuring mode to test mode.
7.3.4 Forcing
Force means that an output of a function can be pre-assigned to a certain value ("0" or "1")
in order to make it easier to carry out troubleshooting, for instance.
Requirements
The following requirements must be met to activate the icons in the toolbar:
The online view is activated.
Test mode is activated on the safety relay.
The logic diagram with the safety circuit is active.
At least one connection of a function is selected.