Diagnostics / service
8.4 Diagnostics with MSS ES
Modular Safety System 3RK3
258 System Manual, 10/2008, 926 2530-02 DS 02
Status Symbol Meaning
Access path to device interface
is open
green The access path over the device interface is open
Disconnect yellow The monitoring time has been exceeded During monitoring time, the safety
relay has not received any data set from the communication partner with
write access to the safety relay.
Handshake error red An error was detected during connection monitoring in test mode.
8.4.1.3 Dialog "Device messages" > "Configuring" tab
The configuration supports the following messages:
General
Status Symbol Meaning
Configuration missing yellow No valid configuration is stored in the safety relay.
Configuration not released yellow A valid configuration is stored but not released yet in the safety relay.
Configuration released green A valid and released configuration is stored in the safety relay.
Max. number of elements
exceeded
red More elements than the maximum number of elements were transferred to
the safety relay.
Max. size of memory exceeded red More element parameters were transferred to the device than can be stored
in the safety relay memory .
Program cycle time exceeded red The program cycle time set by the user is exceeded, MSS changes to
configuring mode.
TARGET configuration equal
ACTUAL configuration
green The specified TARGET configuration of the safety relay corresponds to the
current function and module configuration.
TARGET configuration not equal
ACTUAL configuration
red The specified TARGET configuration of the safety relay does not
correspond to the current function and module configuration.
TARGET slot configuration not
equal ACTUAL slot configuration
red The specified TARGET slot configuration of the safety relay does not
correspond to the ACTUAL slot configuration.
Invalid parameter value red A parameter value is not within the permissible value range.
Factory settings restored green The factory settings were successfully restored.
Password protection
Status Symbol Meaning
Device access authorization
exists
green Device access authorization exists.
Password protection for device
access is inactive
yellow There is no protection against access from a higher-level controller or other
users.
Incorrect password entry yellow A password was received that does not match any device access password
stored in the safety relay.