Description of the software
6.7 Functions
Modular Safety System 3RK3
174 System Manual, 10/2008, 926 2530-02 DS 02
See also
Messages for protective door (Page 265)
6.7.3.6 Enabling button
Description
With the function "Enabling button", the signals from the enabling buttons are evaluated by
means of an NO contact.
An enabling button is always monitored for cross-circuit.
When the enabling button is actuated, the function output Q is activated, i.e. set to "1".
Parameters
Parameter name Description/parameter value
Name You can enter a name for the element here.
Element number Consecutive number which is automatically assigned. You can
change the number.
Element activated When this parameter is active, the function is processed in the
safety logic.
When the parameter is deactivated, the set substitute value is
made available at the output Q.
General
Function output substitute
value
"0" or "1" can be assigned to the substitute value when the
element is deactivated.
Substitute value "0" means output Q = 0
substitute value "1" means output Q = 1
Type Use these parameters to determine the input type of the function:
Single-channel (NO)
IN1 is monitored for "1", i.e. the function output Q is
deactivated when there is a "0" signal.
Two-channel (NONO)
IN1 and IN2 are monitored for "1", i.e. the function output Q is
deactivated when there is at least one "0" signal.
IN1 Select the input to be processed by the function.
Parameter - Input
IN2 Only available with the parameter - Input > Two-channel type
(NONO):
IN2 is automatically assigned depending on the selected input IN1.