Operator control
7.2 Passwords
Modular Safety System 3RK3
210 System Manual, 10/2008, 926 2530-02 DS 02
7.2 Passwords
The configuration and the access to the MSS are subject to special password protection
based on safety technology. You can assign three passwords:
Password for device access (optional)
Password for project access (optional)
Password for changing to test mode (mandatory)
Passwords - Overview
Password for device access Password for project access Password for changing to test
mode
Description
This password prevents
unauthorized access to the
MSS. The password is
assigned when the protection
level is set.
You can control access to the
MSS by setting a protection
level. For the MSS, the
following protection levels can
be set:
Write protection
Project write/read protection
This password protects an
offline configuration from
unauthorized access.
If you do not enter a
password, the configuration is
opened as "read only", i.e.
you cannot change the
configuration
This password prevents an
unauthorized change to "test
mode".
It is only possible to change
to "test mode" if a valid
password has been entered.
If no password has yet been
assigned for test mode, you
have to assign one when
changing to test mode.
The default password is
"0000".
Assigning /
Changing
In MSS ES, via the "Edit" >
"Password for device access"
menu command.
Requirement: You are now in
configuring mode and are online.
In MSS ES, via the "Edit" >
"Password for project access"
menu command.
Requirement: You are now in
configuring mode and are offline.
In MSS ES, via the "Edit" >
"Password for test mode" menu
command.
Requirement: You are now in
configuring mode and are online.
Prompt
Independently of the set
protection level:
When changing the device
access password.
"Write protection" protection
level:
For write access to a safety
relay (e.g. when loading), if
no access rights exist.
Protection level "Project write
protection/read protection":
Just as for the "Write
protection" protection level
When opening an online
configuration
When opening an offline
configuration
When changing the project
access password.
When switching to test mode
via the "Target system" >
"Test mode" menu command.
Validity As long as an access authorization
for the safety relay exists.
As long as the offline
configuration is open.
The password must be re-
entered for each change to test
mode.