Operator control
7.1 Response times
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
209
Minimum actuating duration t
MIN
at the inputs
The minimum actuating duration at the input is the length of time for which a signal must be
present at the input to ensure that it can be reliably detected.
Calculation formula for the minimum actuating duration at the inputs
t
MIN
= 2 x t
CYCL
t
MIN
Minimum actuating duration at the inputs
t
CYCL
Program cycle time of the central unit