Operator control
7
7.1 Response times
Verification of response times in the case of safety circuits
When safety equipment is commissioned, steps must be taken to verify that a safety-related
output will switch off within a maximum permissible response time if the input signal changes
at the relevant input.
To provide this verification, you must calculate the total response time of the application you
have configured.
Note
Note that the calculation of the response time affects the level of safety and governs the
overall design of the system.
Values required for calculating the response time t
R
of the Modular Safety System 3RK3
To calculate the response time t
R
of the MSS, use the following values:
Fixed values:
Output time of the expansion modules (t
OUT
):
◆ Solid-state outputs: 10 ms
◆ Relay outputs: 20 ms
Parameters you assigned during configuration:
Program cycle time t
CYCL
of the central unit: 10 to 60 ms
Input delay t
DELAY
for monitoring functions and input cell at the inputs of the expansion
modules
Timer functions in the logic (timer): t
Timer
066H[SDQVLRQPRGXOH 066FHQWUDOXQLW 066H[SDQVLRQPRGXOH
W
5
[W
&<&/
W
'(/$<
W
7,0(5
=0
,1
(0
287
(0
W
287
Figure 7-1 Maximum response time of the Modular Safety System 3RK3