Description of the software
6.7 Functions
Modular Safety System 3RK3
178 System Manual, 10/2008, 926 2530-02 DS 02
Parameter name Description/parameter value
IN4 Only with switch type 1 out of 4 or 1 out of 5:
Select the input to be processed by the function.
IN5 Only with switch type 1 out of 5:
Select the input to be processed by the function.
Input delay [ms] Select here when the functions further process the signals:
Input delay = "0"
The input signals are further processed by the function without
time delay when there is a signal change.
Input delay not "0"
This parameter can be used to suppress signal interference.
The signal state that was pending for most of the duration of
the input delay is further processed.
Please note that the delay time specified by you is a multiple of the
program cycle time specified by you in the properties of the central
unit.
For additional information on the program cycle time, refer to the
Response times
chapter.