Operator control
7.3 Planning/configuring
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
215
START
Safety mode /
test mode?
Test mode
Safety mode
Check consistency
Ctrl + Alt + K
Load to switching device
Consistent configuration
Online
Go offline
Preparing the
configuration test
Online
Go offline
Enable the
configuration
Test mode
Test mode
Go online
Safety mode
Safety mode
Figure 7-3 Procedure for commissioning the MSS with factory settings
Execute the following steps to start up the device:
Step Action Result
1 Switch on the power supply. The central unit executes a self-test.
2 Open the project in MSS ES. -
3 Choose "Target system" > "Load to switching
device" and confirm the memory dialog with "Yes".
The "Load to switching device" dialog box opens.
4 Set the interface and confirm with "OK". The configuration data is now downloaded. A message is
displayed on completion of the download.
5 Confirm with "OK". You are now online in configuring mode.