Description of the hardware
5.1 Description of the individual modules
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
59
Properties
The DP interface module has the following properties:
The DP interface connects the MSS to PROFIBUS DP and thus with a higher-level
programmable controller.
The DP interface is integrated into the PLC via a GSD file.
You parameterize the DP interface module with MSS ES.
The DP interface is equipped with one system interface for connecting the central unit
and one system interface for connecting a PC/PG.
The DP interface can be used to link non-safety-related signals of a higher-level controller
with the MSS logic.
The DP interface has a baud rate of up to 12 MBit.
The DP interface can carry out the following:
Cyclic: exchange 32 bit process data with the controller.
Acyclic: Query diagnostics data.
The DP interface supports DPV1 and DPV0 mode.
Design of the DP interface module
Front view No. Meaning
(1) Removable terminal block D
(2) Removable terminal block C
(3) System interface X2
(4) PROFIBUS DP connection
(5) Removable terminal block A
(6) Button (SET / MODE)
(7) Inscription label
(8) LCD display
(9) Display LEDs

'3,QWHUIDFH
(10) System interface X1
Terminal designations of the DP interface module
Terminal Meaning Description
L+ Power supply 24 V DC
M Ground Ground to 24 V DC
FE Functional ground Shielding, equipotential bonding