Mounting / connection
4.2 Connection
M200D PROFIBUS/PROFINET
116 Manual, 08/2014, A5E01577426A/RS-AA/004
Requirements
The communication module is mounted on the motor starter module as shown in Chapter
Installing the communication module (Page 99).
You have assigned the device name according to your configuration. Further information:
Assigning IO device names (PROFINET IO) (Page 123)
Required tools
Screwdriver (PZ 2; 2 Nm)
Stripping tool for wiring the M12 and 7/8" cable connectors, if you are fabricating your
own cables.
Required accessories
Prefabricated cable with M12 and 7/8" cable connectors. The cables are available in
different lengths.
If you are fabricating your own cable:
M12: 4-core, shielded bus cable, and decoded M12 cable connector (PROFINET)
7/8": 4-core cable with 7/8" cable connectors
Pin assignment of the M12 and 7/8" cable connectors
PROFINET connection (M12)
Each port is connected via an M12 socket (D coding).
Pin
Assignment
M12-D
1 Transmission data + (TD+)
2 Receive data + (RD+)
3 Transmission data – (TD–)
4 Receive data (RD–)