Functions
3.10 Communication over PROFIBUS/PROFINET
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
69
Parameter block CPU/master OFF Motor starter accepts the parameters from the master (PLC)
Parameter block CPU/master ON Motor starter ignores the parameters from the master (PLC)
Delete Logbook - Triggering
operations
Delete logbook with recorded fault causes
Delete Logbook - Events Delete logbook with recorded warnings and specific actions
Cold run ON Enables activation of the switching contacts without main
power
Cold run OFF Switches the "cold run" function off
Delete maintenance timer Deletes the timer of the maintenance function
Data plausibility check
Description
The motor starter checks all incoming parameters for validity and plausibility.
In the case of incorrect parameters
● During starting (after Power ON), the messages "Group fault" and "Invalid parameter
value" are set.
The motor and the brake output remain switched off.
● During operation, the messages "Invalid parameter value" or "Parameter assignment not
possible in ON state" are set. "Group fault" is not set.
The motor and the brake output are not switched off.
The currently valid parameter values are retained.