EasyManua.ls Logo

Siemens SIRIUS M200D - Appendix

Siemens SIRIUS M200D
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
189
Statistical data on device service life
Operating hours
The motor starter records 2 operating hours values:
The operating hours of the motor.
This indicates how long the motor was switched on.
The operating hours of the device (motor starter).
Indicates how long the 24 V DC LV power supply of the motor starter was switched on
Both operating hours values are recorded in data set 95 Statistics. They are entered in the
data field "Operating hours" alternately at 5-second intervals. The bit "Operating hours
selection" specifies which of the two operating hours values has been transferred.
[0]: Operating hours - motor
[1]: Operating hours - device
The operating hours are recorded in the range from 0 to 16,777,215 minutes in 1-second
steps.
Number of overload trips
The motor starter counts the number of overload trips in the range 0 to 65,535.
Number of starts motor CW/CCW
The motor starter counts the number of starts in the range 0 to 16,777,215.
Example: The value is incremented by 1 when the current is flowing in the main circuit
after the "Motor ON" command has been issued.
Motor current I
max
.
The motor starter measures the current in all 3 phases and displays the current of the
phase under the greatest load as a percentage [%] of the setting current I
e
.
Data format: 1 byte, 8-bit current format
Example: Setting current I
e
= 10 A
Indicated motor current 110%
then corresponds to 10 A x 1.1 = 11 A
All 3 phase currents are available in data set 94
Last tripping current
The motor starter measures the current in all 3 phases and displays the current that is
flowing in the phase under the greatest load when the trip occurs as a percentage [%] of
the current setting I
e
and in amperes [A]
Data format: 2 bytes, 9-bit current format
Example: Setting current I
e
= 10 A
Indicated motor current 455% then corresponds to 10 A x 4.55 = 45.5 A

Table of Contents

Related product manuals