Diagnostics
7.1 Diagnostics with LED
M200D PROFIBUS/PROFINET
140 Manual, 08/2014, A5E01577426A/RS-AA/004
7.1
Diagnostics with LED
7.1.1
Statuses of the individual LEDs
The following LEDs indicate the status of the motor starter:
Figure 7-1 Diagnostic LEDs
SF LED (possible colors: red / OFF)
Status
Meaning
Possible causes
Off No error No error is present
Red Device detects error Device error:
Current flowing with no ON command
Self-test error
System error:
Current not flowing despite ON command
(residual current detected)
Thermal motor model overload
1)
Temperature sensor overload
1)
Asymmetry detected
1)
Current limit violation
1)
Connector monitoring
1)
Circuit breaker tripped/switched off
1)
Group fault via output action
External encoder supply short-circuit
Internal trip
No switching element supply voltage (DC24V S)
1)
No electronics supply voltage (D24-V-NS)
1)
Start-up fault:
Start-up parameters missing
1)
Depends on the parameter assignment