M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
139
Diagnostics
7
The M200D motor starter has the following diagnostics modes:
Diagnostics with LED (Page 140)
Diagnostics as device diagnostics
Diagnostics via system diagnostics
The structure of system diagnostics is manufacturer-independent (PROFIBUS standard
diagnostics).
The contents of individual bytes, however, are defined by the manufacturer.
Diagnostics via data sets
Diagnostics can be read out from data sets regardless of the system diagnostics.
Actions after a diagnostics message
Each diagnostic message triggers the following actions:
The SF LED (red) of the I/O device lights up.
Several simultaneous diagnostic messages are possible.
Diagnostics data is reported as diagnostics interrupts and can be read from data sets (if
group diagnostics are enabled).
Diagnostics messages are saved to the diagnostics buffer of the I/O controller.
OB 82 is called. If OB 82 is not available, the I/O controller switches to the STOP
operating state.
Acknowledgment of the diagnostics interrupt to enable new interrupts.