Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
127
5.2.2
Parameter overview
More information on the individual parameters can be found in Chapter Functions (Page 25).
The table below provides an overview of all parameters of the
M200D PROFIBUS/PROFINET motor starter.
Device parameter
Default setting
Setting range
Basic functions / parameters (Page 27)
Rated operating
current
In the motor starter:
maximum value
In GSD/Motor Starter ES:
minimum value
0.15 A to 2.0 A
1.5 A to 9.0 A
1)
1.5 A to 12.0 A
Increment: 10 mA
Load type 3-phase
3-phase
1-phase
Protection against
voltage failure
Yes
Yes
No
Response to no
switching element
supply voltage
Group fault
Group fault
Group fault only after ON command
Group warning
Fieldbus interface (Page 31)
Response to
CPU/master STOP
Switch substitute value
Switch substitute value
Retain last value
Substitute value 0 8 bits (0 or 1)
Group diagnostics block
block
enable
Motor control (Page 33)
Lock-out time 0 0 to 60 s increment: 1 s
Starting time (x 0.25 s) 5 s 0 to 30 s increment: 0.25 s
Run-down time 0 0 to 30 s increment: 0.25 s
Startup mode direct
direct
Voltage ramp
Current limiting
Voltage ramp + current limiting
Run-down type Run-down without load
Run-down without load
Voltage ramp
Starting voltage 40 % 20 % to 100 % increment: 5 %
Stopping voltage 40 % 20 % to 90 % increment: 5 %