Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
127
More information on the individual parameters can be found in Chapter Functions (Page 25).
The table below provides an overview of all parameters of the
M200D PROFIBUS/PROFINET motor starter.
Basic functions / parameters (Page 27)
Rated operating
current
• In the motor starter:
maximum value
• In GSD/Motor Starter ES:
minimum value
• 0.15 A to 2.0 A
• 1.5 A to 9.0 A
1)
• 1.5 A to 12.0 A
Increment: 10 mA
Load type 3-phase
• 3-phase
• 1-phase
Protection against
voltage failure
Yes
• Yes
• No
Response to no
switching element
supply voltage
Group fault
• Group fault
• Group fault only after ON command
• Group warning
Fieldbus interface (Page 31)
Response to
CPU/master STOP
Switch substitute value
• Switch substitute value
• Retain last value
Substitute value 0 8 bits (0 or 1)
Group diagnostics block
• block
• enable
Motor control (Page 33)
Lock-out time 0 0 to 60 s increment: 1 s
Starting time (x 0.25 s) 5 s 0 to 30 s increment: 0.25 s
Run-down time 0 0 to 30 s increment: 0.25 s
Startup mode direct
• direct
• Voltage ramp
• Current limiting
• Voltage ramp + current limiting
Run-down type Run-down without load
• Run-down without load
• Voltage ramp
Starting voltage 40 % 20 % to 100 % increment: 5 %
Stopping voltage 40 % 20 % to 90 % increment: 5 %