Functions
3.21 PROFIenergy
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
85
3.21.2
PROFIenergy (version V1.0) in the M200D PROFINET motor starter
The M200D PROFINET motor starter supports the "PE_Energy_saving_function" and
"PE_Measured_value_function" for the motor current. These are identified as commands,
since they trigger reactions in the M200D motor starter.
In addition, the M200D motor starter also provides so-called services, which provide
information on the status of the motor starter as defined in PROFenergy. These can then be
evaluated and further processed in the user program.
Commands
The following commands are supported:
Control commands
Start_Pause The starter switches to energy-saving mode.
End_Pause The starter switches back to operating mode.
Status commands
PE_Identify Provides a list of supported PROFIenergy commands/functions.
PEM_Status Shows the status of the current PE mode.
Query_Modes
List_Energy_Saving_Modes Provides a list of supported energy-saving modes.
Get_Mode Provides the parameter values with which the
PE_Energy_saving_function works.
Query_Measurement
Get_Measurement_List Provides a list of supported PE_Measured_values
Get_Measurement_Values Shows the supported PE_Measured_values
The M200D motor starter distinguishes between two different statuses for data transmission:
PE_Mode_ID = 255 Ready to operate
PE_Mode_ID = 01 Energy-saving mode