Functions
3.21 PROFIenergy
M200D PROFIBUS/PROFINET
86 Manual, 08/2014, A5E01577426A/RS-AA/004
t
off
Time_to_Pause Time the starter requires in order to change to power saving
mode. This time is always 100 ms for M200D. A
parameterized running down time is added to this in the
case of a soft starter (if available and if the starter was in the
ON state):
t
off
= 100 ms + running down time
If the soft starter was already off before the pause, pause
mode will be switched to after 100 ms only.
t
off_min
Time_min_length_of_stay Minimum time that the device spends or should spend in
saving mode.
t
on
Time_to_operate Time that will elapse before the starter changes back to the
operating state. Since the process image is evaluated again
immediately when the M200D exits power saving mode, this
t
Pause_min
Time_min_Pause Time that is compared with t
Pause
(is transferred together
with the "Start_Pause" command to the motor starter);
if t
Pause
≥ t
Pause_min
, the device switches to saving mode.