DS96 Read maximum pointer
The extreme values of individual values measured in the elapsed time are stored in the
maximum pointers. Maximum pointers can be deleted or set to "0" by the user with the
command "Delete maximum pointers".
Statistics data for for preventive diagnostics (maximum pointer)
Object No.
Byte.Bit
Maximum pointer
Value range/[encoding]
Increment
Relevant for
0 ... 3 Reserved (0x00)
656 4 Phase current I
L1 min
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
657 5 Phase current I
L2 min
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
658 6 Phase current I
L3 min
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
653 8 Phase current I
L1 max
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
654 9 Phase current I
L2 max
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
655 10 Phase current I
L3 max
(%) 0 ... 796.9 % / [unsigned 8] 3.125 % All
652 12 ... 13 Maximum tripping current
I
A max
(%)
0 ... 1 000 % / [unsigned 16] 3.125 % All
651 14 ... 15 Number of motor overload trips 0 ... 65535 / [unsigned 16] 1 All
659 16 ... 19 Maximum tripping current
I
A max
(rms)
± 0 ... 20000 A / [signed 32] 0.01 A All
660 20 ... 23 Phase current I
L1 min
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
661 24 ... 27 Phase current I
L2 min
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
662 28 ... 31 Phase current I
L3 min
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
663 32 ... 35 Phase current I
L1 max
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
664 36 ... 39 Phase current I
L2 max
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
665 40 ... 43 Phase current I
L3 max
(rms) ± 0 ... 20000 A / [signed 32] 0.01 A All
674 60 Maximum heat sink temperature -40 ... +127 °C / [signed 8] 1°C sRSSte/sDSSte
12 A
678 64 ... 67 Operating hours motor current
= 18 to 49.9% x I
e
0 ... 4 294 967 295 /
[unsigned 32]
1 s / 1 min All
1)
679 68 ... 71 Operating hours motor current
= 50 to 89.9 % x I
e
0 ... 4 294 967 295 /
[unsigned 32]
1 s / 1 min All
1)
680 72 ... 75 Operating hours motor current
= 50 to 119.9 % x I
e
0 ... 4 294 967 295 /
[unsigned 32]
1 s / 1 min All
1)
681 76 ... 79 Operating hours motor current
= 120 to 1000 % x I
e
0 ... 4 294 967 295 /
[unsigned 32]
1 s / 1 min All
1)
1)
Resolution is signaled via infobit "Operating hours resolution" in DS 94.